FIELD SURVEY OF EXISTING CONDITIONS (in Year 1999)
1.0 CHILLER DESIGN DATA and OPERATING DATA
1.1 Existing Equipment for Chilled Water System
The Central Chilled Water System comprises of:
• 5 units 750 Tons Centrifugal Chillier.
• 5 units 55KW Chilled Water (CHW) pumps.
• 4 units 45KW Condenser water (CW) pumps and 1 unit 55KW Condenser water (CW) pump.
Chilled Water Plant Operation:
During the time of survey, there are 3 chillers, 3 CHW pumps and 3 CW pumps in 24 hours operation. All the data listed below were collected from Chiller # 2 & CHWP # 2 .
1.2 Design Data:
| Chiller Design Data |
Design Flow |
Design Pressure Drop |
| Evaporator |
1,500 USGPM (95 L/s) |
30.0 ft WG (12.9 psi) |
| Condenser |
2,250 USGPM (142 L/s) |
12.3 ft WG (5.3 psi) |
1.3 Actual Operating Data:
| Chiller Operating Data |
Operating Pressure Drop |
| Evaporator |
26.0 psi |
| Condenser |
5.0 psi |
2.0 PRIMARY CHILLED WATER PUMPS
2.1 Design Data
| Pumps |
Design head |
Design flow |
Powe/Fla |
| CHWP 2 |
124 ft WG |
95 L/s (1500 USGPM |
55KW / 99A |
2.2 Actual operating conditions :
i) Valve Balanced (partially throttled)
| Pumps |
Actual head |
Actual flow |
VAC / FLA / Consumed Power |
| CHWP 2 |
124 ft WG |
95 L/s (1500 USGPM) |
441VAC / 74.9A / 49.8KW |
An Energy Saving Software (HVAC Tool Box II) was used to calculate the energy consumption.



ii) Valve Fully Open
| Pumps |
Actual head |
Actual flow |
VAC / FLA / Consumed Power |
| CHWP 2 |
112 ft WG |
119 L/s (1880 USGPM) |
119 L/s (1880 USGPM) |


Analysis and re
commendations:
Based on the above collected data, the
actual flow of chilled water circuit appears to be higher
than the design flow (approximately 25% over the design
flow). In order to avoid wasting the energy by pumping
extra water in the chilled water circuit, variable speed
drive (VSD) was recommended to be fixed to the chilled
water pumps to bring the actual flow of chilled water
circuit back to the design.
This will help to reduce the energy consumption of the
pump and improve the
efficiency of the chiller due to the improved performance
of heat exchanger.
3.0 Energy Consumption for Chilled Water Pump:
Annual power consumption of each CHWP = 430,118 KWH /year
Annual power consumption of each CHWP
installed with VSD = 298,829 KWH /year
Total KWH saving for each CHWP = 131,289 KWH/year
Total KWH saving for 3 units CHWP = 3 x 131,289 KWH/year
= 393,867 KWH/year
Amortisation Analysis:
Electricity
cost (Tariff C2): RM 0.128 / KWHr (Off-peak Period)
RM 0.208 / KWHr (Peak Period)
RM 25.70 / KWHr (Maximum Demand)
Annual
cost saving =
(393,867 x 0.128 x 14 / 24) + (393,867 x 0.208 x 10
/ 24) + (393,867/ 8760 x 25.70 x 12)
= RM 29,408.74 + RM 34,135.14 + RM 13,866.27 =
RM 77,410.15
Total
installation cost (VSD + panel modification + sensors
+ system balancing ) = RM140,000
Therefore,
Return of Investment (ROI) = Savings/Investment = <1.9
year
Source: Danfoss Industries Sdn Bhd |